Reference Guide

Container OS Architecture

Standardized electromechanical platform for ISO 20ft high-cube shipping containers. 380VDC backbone (ETSI EN 300 132-3). Cassette + backplane architecture: 4 base slots (A-Power, B-Control, C-HVAC, D-Comms) + 2 application slots (E, F).

6 Application Profiles

  • Edge Data Center — 630A, 200kW payload, liquid cooling (CDU)
  • Vertical Farm — 250A, LED grow lights, hydroponics
  • BESS — 125A, LFP battery storage, strict thermal management
  • Habitation Pod — 63A, living space, kitchen, bathroom
  • Micro-Factory — 250A, CNC, 3D printing, compressed air
  • Field Hospital — 125A, medical gas, HEPA, extended UPS

HVAC Tiered Cooling

Three-tier HVAC reduces energy 40-70% annually. Tier 1: Thermosiphon (passive, <15°C ambient). Tier 2: Economizer (fan only, 15-25°C). Tier 3: Compressor (full mechanical, >25°C). COP formula: rated_COP × (1 - 0.018 × (T_ambient - 35)).

Cascade Failure Defense

Three layers of defense against HVAC failure. Layer 1: Auto load-shed (5s) — contactors drop payload. Layer 2: Emergency ventilation (10s) — spring-loaded damper + DC fan. Layer 3: Equipment thermal mass — 500kg of steel/copper provides 14× the thermal capacitance of air alone.

3D Twin Layers

  • Cables — 3 segregated cable tray zones with separation gaps
  • EMI — VFD exclusion volumes, power cable zones
  • Airflow — Supply/return/condenser particle streams
  • Refrigerant — R1234ze tube loop with flow particles
  • Power — 380VDC busbar particles, branch utilization
  • Thermal — Floor/ceiling temperature gradients
  • State — Firmware state badges per cassette

Key Specs

  • Container: ISO 20ft HC (6058×2438×2896mm)
  • Insulation: 50mm closed-cell SPF (R-2.3 m²K/W)
  • Refrigerant: R1234ze (GWP=1, A2L)
  • Connectors: Anderson SB175 (silver-plated)
  • PLC: Beckhoff TwinCAT CX-series + TwinSAFE
  • PCM Buffer: 10kg RT28 (2MJ latent heat)